Artikel 0
2204
 

2204

 

Isolation amplifier

 

  • Input galvanically separated from output and supply
  • Current or voltage input
  • Signal conversion
  • Current and voltage output
  • 24 VDC supply or universally supplied
  • Applicable in PELV/SELV circuits
  1. Overview

  2. Technical details

  3. Accessories


Advanced features

  • Factory-calibrated measurement ranges for input and outputs in the 2204 can be selected by the internal DIP-switches without the need for recalibration.

Application

  • Signal isolator for analog current / voltage signals.
  • 1 : 1 or signal conversion of analog current /voltage signals within the ranges: 0...10 VDC or 0...50 mA on the input and 0...20 mA and 0...10 VDC in fixed ranges on the output.
  • Analog signal conditioning with microprocessor based gain and zero offset giving a response time of less than 25 ms.

Technical characteristics

  • Universally supplied units have a 3-port galvanic separation between input, supply, and output.
  • Mounting for a standard 11-pole socket which can be adapted for DIN rail or plate use with PR’s 7023 adaptor and 7024 mounting keying.

Environmental Conditions

Operating temperature -20°C to +60°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP50

Mechanical specifications

Dimensions (HxWxD) 80.5 x 35.5 x 84.5 mm (D is without pins)
Weight DC / universally supplied 110 g / 160 g

Common specifications

Supply

Supply voltage 19.2...28.8 VDC
Supply voltage, universal 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC
Internal power dissipation ≤ 1.3 W (2204--D ) ≤ 1.8 W (2204--P)

Isolation voltage

Isolation voltage, test / working 3.75 kVAC / 250 VAC
PELV/SELV IEC 61140

Response time

Response time (0...90%) < 25 ms
Accuracy Better than 0.1% of selected range
Signal / noise ratio Min. 60 dB
Temperature coefficient < ±0.01% of span / °C
Linearity error < 0.1% of span
Effect of supply voltage change < ±0.002% of span / %V
EMC immunity influence < ±0.5% of span

Input specifications

Common input specifications

Max. offset 20% of max. value

Current input

Measurement range 0...50 mADC
Min. measurement range (span) 4 mA
Input resistance Nom. 50 Ω

Voltage input

Measurement range 0...10 VDC
Min. measurement range (span) 0.2 VDC
Input resistance 10 MΩ

Output specifications

Current output

Signal range 0...5 mA / 0...20 mA
Min. signal range 4 mA / 16 mA
Load (@ current output) ≤ 600 Ω
Load stability ≤ 0.01% of span / 100 Ω
Current limit 23...28 mA
*of span = of the presently selected range

Observed authority requirements

EMC 2014/30/EU
LVD 2014/35/EU
EAC TR-CU 020/2011
Ihre Anfrage wurde erfolgreich versendet - 0 Artikel in Ihrer Liste
Produktbeschreibung Stückzahl
Bitte spezifizieren Sie eine Variante (siehe Datenblatt) – oder wählen Sie „Variante unbekannt“
Ihre Kontaktdaten
Weitersuchen
Keine Artikel ausgewählt….
Es befinden sich keine Artikel in Ihrer Liste…

Von den produktbezogenen Seiten auf unserer Homepage können Artikel zu der Liste hinzugefügt und uns diese Liste zugeschickt werden. Hierdurch wird ein Angebot eingeholt. Sie fügen Artikel zu Ihrer Liste hinzu, indem Sie auf der individuellen Produktseite das Feld “Anfrage stellen” anklicken.

Sobald uns die Liste zugeschickt wurde, werden wir uns schnellstmöglich mit Ihnen in Verbindung setzen.

Sollte uns die Liste nicht zugeschickt werden, so steht Sie Ihnen für eine Dauer von 7 Tagen zur Verfügung (Dies ermöglicht die Cookie-Technik auf Ihrem PC bzw. Tablet)
Wir hoffen, dass Ihnen diese Funktion nützlich ist. Bitte fügen Sie Artikel über die Produkt-Seiten zur Liste hinzu.
Vielen Dank für Ihre Anfrage.
Wir werden uns schnellstmöglich per Telefon oder per E-Mail mit Ihnen in Verbindung setzen.