Artikel 0
2279
 

2279

 

AC / DC transmitter

 

  • Input galvanically separated from output and supply
  • AC current measurement
  • AC voltage measurement
  • Current and voltage output
  • 24 VDC supply or universally supplied
  • Applicable in PELV/SELV circuits
  1. Overview

  2. Technical details

  3. Accessories


Advanced features

  • ±20% adjustment of the 0 and the 100% measurement range is possible at the front panel.
  • Input and output ranges are programmable by use of internal DIP-switches.

Application

  • AC current measurement e.g. in connection with a current transformer or a current clamp.
  • Direct AC voltage measurement.

Technical characteristics

  • Analog signal conditioning with microprocessor based gain and zero offset.
  • Signals in the ranges 0.5...250 VRMS sinusoidal voltage can be connected directly to the input, ranges are programmed via DIP-switches and jumpers.
  • Analog standard current output of 0/4...20 mA or standard voltages of 0...1 or 0...10 VDC ranges are programmed via DIP-switches and jumpers.
  • Special currents and voltages within the signal range.
  • Signal reversal e.g. 20...4 mA is possible in a special version.
  • Universally supplied units have a 3-port galvanic separation between input, supply, and output.
  • Mounting for a standard 11-pole socket which can be adapted for DIN rail or plate use with PR’s 7023 adaptor and 7024 mounting keying.

Environmental Conditions

Operating temperature -20°C to +60°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP50

Mechanical specifications

Dimensions (HxWxD) 80.5 x 35.5 x 84.5 mm (D is without pins)
Weight DC / universally supplied 100 g / 160 g

Common specifications

Supply

Supply voltage 19.2...28.8 VDC
Supply voltage, universal 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC
Max. required power ≤ 1.3 W (2279--D) ≤ 2.7 W (2279--P)

Isolation voltage

Isolation voltage, test / working 3.75 kVAC / 250 VAC
PELV/SELV IEC 61140

Response time

Response time (0...90%) < 1.5 s
Signal / noise ratio Min. 60 dB
Effect of supply voltage change < 0.005% of span / VDC
Temperature coefficient < ±0.01% of span / °C
Linearity error < ±1% of span
EMC immunity influence < ±0.5% of span

Input specifications

Common input specifications

Max. offset 50% of max. value

Current input

Measurement range 0...1 ARMS / 40...400 Hz
Min. measurement range (span) 500 mARMS
Input resistance Nom. 1 Ω

Voltage input

Measurement range 0...250 VRMS / 40...400 Hz
Min. measurement range (span) 0.5 VAC
Input resistance > 1 MΩ

Output specifications

Current output

Signal range 0...5 mA / 0...20 mA
Min. signal range 4 mA / 16 mA
Load (@ current output) ≤ 600 Ω
Load stability ≤ 0.01% of span / 100 Ω
Current limit 23...28 mA
Voltage output through internal shunt See manual for details
*of span = of the presently selected range

Observed authority requirements

EMC 2014/30/EU
LVD 2014/35/EU
EAC TR-CU 020/2011
Ihre Anfrage wurde erfolgreich versendet - 0 Artikel in Ihrer Liste
Produktbeschreibung Stückzahl
Bitte spezifizieren Sie eine Variante (siehe Datenblatt) – oder wählen Sie „Variante unbekannt“
Ihre Kontaktdaten
Weitersuchen
Keine Artikel ausgewählt….
Es befinden sich keine Artikel in Ihrer Liste…

Von den produktbezogenen Seiten auf unserer Homepage können Artikel zu der Liste hinzugefügt und uns diese Liste zugeschickt werden. Hierdurch wird ein Angebot eingeholt. Sie fügen Artikel zu Ihrer Liste hinzu, indem Sie auf der individuellen Produktseite das Feld “Anfrage stellen” anklicken.

Sobald uns die Liste zugeschickt wurde, werden wir uns schnellstmöglich mit Ihnen in Verbindung setzen.

Sollte uns die Liste nicht zugeschickt werden, so steht Sie Ihnen für eine Dauer von 7 Tagen zur Verfügung (Dies ermöglicht die Cookie-Technik auf Ihrem PC bzw. Tablet)
Wir hoffen, dass Ihnen diese Funktion nützlich ist. Bitte fügen Sie Artikel über die Produkt-Seiten zur Liste hinzu.
Vielen Dank für Ihre Anfrage.
Wir werden uns schnellstmöglich per Telefon oder per E-Mail mit Ihnen in Verbindung setzen.