Artikel 0
2261
 
 

2261

 

mV transmitter

 

  • Load cell amplifier
  • mV to current / voltage conversion
  • Front-programmable / LED display
  • Relative calibration of input span
  • NPN / PNP input for external taring
  • Supply for standard transducers
  1. Overview +

  2. Technical details +

  3. Accessories +


Advanced features

  • A multifunction user interface consisting of three pushbuttons and a 3-digit LED display for programming.

Application

  • The 2261 converts bipolar mV signals from transducers supplied directly by the device to standard current / voltage signals.
  • The 2261 is suitable for load cell application as well as other applications such as tank filling and draining, weighing with a taring function, measurement of cable tensile force, level control, signal conversion / amplification etc.

Technical characteristics

  • Front error LED.
  • The analog input can be programmed for voltage in the range -40...100 mVDC.
  • The digital signal can be selected as either NPN or PNP.
  • Taring can either be by way of the digital input or from the front interface.
  • The analog output can be programmed to current in the range 0...20 mA or voltage in the range 0...10 VDC.
  • Transducer supply which can be programmed to 5...13 VDC from the front. It is up to the customer to ensure a max. load of 230 mA (e.g. 6 parallel 350 Ω load cells).
  • Sense input (with transducer supply used) for compensation for cable resistance to the transducer.
  • Mounting for a standard 11-pole socket which can be adapted for DIN rail or plate use with PR’s 7023 adaptor and 7024 mounting keying.

Environmental Conditions

  • Operating temperature

    -20°C to +60°C

  • Calibration temperature

    20...28°C

  • Relative humidity

    < 95% RH (non-cond.)

  • Protection degree

    IP50

Mechanical specifications

  • Dimensions (HxWxD)

    80.5 x 35.5 x 84.5 mm (D is without pins)

  • Weight approx.

    130 g

Common specifications

  • Supply

  • Supply voltage

    19.2...28.8 VDC

  • Max. required power

    7.2 W

  • Internal power dissipation

    2.2 W

  • Response time

  • Response time (programmable)

    0.06...999 s

  • Signal / noise ratio

    Min. 60 dB

  • Updating time

    20 ms

  • Signal dynamics, input

    17 bit

  • Signal dynamics, output

    16 bit

  • Effect of supply voltage change

    < ±0.002% of span / %V

  • Temperature coefficient

    < ±0.01% of span / °C

  • Linearity error

    < 0.1% of span

  • Auxiliary voltage: Transducer supply

    5...13 VDC

  • Load (max.)

    230 mA

  • EMC immunity influence

    < ±0.5% of span

Input specifications

  • Common input specifications

  • Max. offset

    70% of selec. max. value

  • Voltage input

  • Measurement range

    -40...100 mV

  • Min. measurement range (span)

    10 mV

  • Input resistance

    > 10 MΩ

  • Overrange

    0...999% of selected measurement range

  • NPN, digital input

    Pull up 24 VDC / 6.9 mA

  • PNP, digital input

    Pull down 0 VDC / 6.9 mA

  • Trig level low, NPN/PNP

    < 6 VDC

  • Trig level high, NPN/PNP

    > 10.5 VDC

  • Pulse length

    > 30 ms

Output specifications

  • Current output

  • Signal range

    0...20 mA

  • Min. signal range

    5 mA

  • Load (@ current output)

    ≤ 600 Ω

  • Load stability

    ≤ 0.01% of span / 100 Ω

  • Current limit

    < 23 mA

  • Voltage output through internal shunt

    See manual for details

  • of span

    = of the presently selected range

Observed authority requirements

  • EMC

    2014/30/EU

  • EAC

    TR-CU 020/2011

Ihre Anfrage wurde erfolgreich versendet - 0 Artikel in Ihrer Liste
Produktbeschreibung Stückzahl
Bitte spezifizieren Sie eine Variante (siehe Datenblatt) – oder wählen Sie „Variante unbekannt“
Ihre Kontaktdaten
Weitersuchen
Keine Artikel ausgewählt….
Es befinden sich keine Artikel in Ihrer Liste…

Von den produktbezogenen Seiten auf unserer Homepage können Artikel zu der Liste hinzugefügt und uns diese Liste zugeschickt werden. Hierdurch wird ein Angebot eingeholt. Sie fügen Artikel zu Ihrer Liste hinzu, indem Sie auf der individuellen Produktseite das Feld “Anfrage stellen” anklicken.

Sobald uns die Liste zugeschickt wurde, werden wir uns schnellstmöglich mit Ihnen in Verbindung setzen.

Sollte uns die Liste nicht zugeschickt werden, so steht Sie Ihnen für eine Dauer von 7 Tagen zur Verfügung (Dies ermöglicht die Cookie-Technik auf Ihrem PC bzw. Tablet)
Wir hoffen, dass Ihnen diese Funktion nützlich ist. Bitte fügen Sie Artikel über die Produkt-Seiten zur Liste hinzu.
Vielen Dank für Ihre Anfrage.
Wir werden uns schnellstmöglich per Telefon oder per E-Mail mit Ihnen in Verbindung setzen.